The TU850 MTU can have up to 16 I/O channels. The maximum rated voltage is 50 V and maximum rated current is 15mA per I/O channel (digital input) or 25mA per two I/O channels (analog input).
The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU.
The MTU can be mounted on a standard DIN rail. It has a mechanical latch that locks the MTU to the DIN rail. Two mechanical keys are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and Benefits
Complete 2-wire connections for up to 16 channels.
Each channel has one current limited sensor/transmitter power outlet terminal and one signal terminal.
Current limitation in sensor/transmitter supply is implemented with disconnectable PTC fuse.
Process voltage can be connected to 2 individually isolated groups, if the I/O module supports it.
Connections to ModuleBus and I/O modules.
Mechanical keying prevents insertion of the wrong I/O module.
Latching device to DIN rail for grounding.
DIN rail mounting.
Article number
3BSE050930R1
Type
Extended
Connection
Terminal block
Channels
16
Voltage
50 V
Mounting
Both directions
Mounting detail
55 º (131 °F)
Use with I/O
AI810, DI810, DI811,DI830, DI831
Process connections
40 up to 16 I/O channels 16 current limited sensor/transmitter power outlets D-sub connectors 25 pin (male)