S800 I/O- TU811V1
The TU811V1 is a 8 channel 250 V compact module termination unit (MTU) for the S800 I/O. The MTU is a passive unit used for connection of the field wiring to the I/O modules. It also contains a part of the ModuleBus.
The MTU distributes the ModuleBus to the I/O module and to the next MTU. It also generates the correct address to the I/O module by shifting the outgoing position signals to the next MTU.
Two mechanical keys are used to configure the MTU for different types of I/O modules. This is only a mechanical configuration and it does not affect the functionality of the MTU or the I/O module. Each key has six positions, which gives a total number of 36 different configurations.
Features and Benefits
- Compact installation of I/O modules.
- Up to 8 isolated channels of field signals.
- Connections to ModuleBus and I/O modules.
- Mechanical keying prevents insertion of the wrong I/O module.
- Latching device to DIN rail for grounding.
- DIN rail mounting.
Article number | 3BSE0
| ||||||||||||||||||
Type | Compact | ||||||||||||||||||
Connection | Terminal block | ||||||||||||||||||
Channels | 16 | ||||||||||||||||||
Voltage | 50 V | ||||||||||||||||||
Mounting | Both directions | ||||||||||||||||||
Mounting detail | Horizontal 55 ºC (131 °F) Vertical 40 ºC (104 °F) |
||||||||||||||||||
Use with I/O | AI810, AI815, AI820, AI830, AI830A, AI835, AI835A, AI845, AO810, AO810V2, AO815, AO820, AO845, AO845A, DI810, DI811, DI814, DI830, DI831, DI840, DI880, DI885, DO810, DO814, DO815, DO840, DO880, DP820, DP840 | ||||||||||||||||||
Process connections | 2 x 2 Process power, 5 x 2 Process power (0 V) | ||||||||||||||||||
Single/redundant I/O | Single |